In a nutshell
- Snow load: Greenlandic projects are typically designed for 2.5–4.0 kN/m² vs. Denmark's 0.9–1.2 kN/m²
- Wind load: Wind speeds up to 55+ m/s in exposed areas vs. 24–27 m/s in Denmark
- Zone-specific: Roof and façade are dimensioned to local data — not a single Greenlandic baseline
- EN 1991: The standard applies in Greenland too — only the values are higher
- CemPU's capacity: Standard elements are dimensioned for arctic loads from production — project-specific documentation is delivered with drawings
How high are snow and wind loads in Greenland?
Snow load and wind load are two of the most project-defining design parameters in Greenlandic construction. Where a Danish construction is typically designed for a snow load around 0.9–1.2 kN/m² and a wind speed around 24–27 m/s, Greenlandic projects can be at 2.5–4.0 kN/m² snow load and wind speeds up to 55+ m/s in exposed areas.
These values cannot be ignored — they determine element thickness, anchoring, joints and spans.
What determines the snow load in a Greenlandic project?
Snow load is calculated per EN 1991-1-3 with project-specific parameters:
- Characteristic snow load on the ground for the specific geography — varies considerably from fjord to mountain
- Exposure — exposed or sheltered location
- Roof shape and pitch — flat roofs collect more snow than steep ones
- Thermal coefficient — how warm the building is internally
- Drift and accumulation phenomena — snow that gathers on lower roof surfaces from higher ones
In Greenland it is entirely common to see design snow loads of 3.0 kN/m² and above for roofs and 2.5 kN/m² and above for wall load under particular conditions.
What determines the wind load in a Greenlandic project?
Wind load is calculated per EN 1991-1-4 with:
- Basic wind speed for the area — in certain Greenlandic areas can be above 50 m/s
- Terrain category — exposed coastal or inland
- Height profile — wind speed increases with height
- Building geometry — angles, openings and curvatures give wind concentrations
In particularly exposed areas (fjord mouths, high points), the design wind load can be 2–3 times higher than typical Danish values.
How are CemPU elements dimensioned for arctic loads?
CemPU consists of stiff sandwich elements that are themselves very strong — the solid cement facing gives high load-bearing capacity in both bending and shear. But the design is not only about the element itself, also about:
- Anchoring in the foundation — wind load must be transferred without uplift
- Joints element-to-element — bracing the building's overall stability
- Connections to roof and floor — ensuring that the entire construction acts as a single stiffness system
- Openings — windows and doors must be designed for the local wind load
How does Tekment document load dimensioning per project?
For each Greenlandic project, Tekment prepares structural documentation that directly addresses BR2006:
- Calculation basis per EN 1991 (Eurocode 1)
- Project-specific snow load and wind load for the building site coordinates
- Load-bearing capacity per element type and span
- Joint and anchoring details documented per connection
- Stamped and signed by a structural engineer
This reduces the consultant's need for project-specific check calculation and accelerates the authority's processing.